Non-sheathed cables >> 60227 IEC 08

Single-core non-sheathed cables with solid conductor for internal wiring for a conductor temperature of 90°C.

Application:
- In dry rooms, apparatus, switch and distribution boards, for fixed installation in conduits, over and under plaster and on insulated supports over plaster. Direct laying in plaster is not permitted.
- Minimum bending radius: 4 times of maximum overall diameter.

Standard:
- ISIRI (607)08
- IEC (60227)08
- H05V2-k
Construction:
- Annealed stranded copper conductor, class 5.
- PVC insulation, type E.

Cross-
sectional
area
Nom.
No. of
wires x
diameter
Nom.
Insulation
thickness
Nom.
Overall
diameter
Max.
Insulation
resistance
at 70°C
Min.
Weight
Nom.
mm2
mm
mm
mm
kg/km
0.5
16 x 0.20
0.6
2.5
0.013
9
0.75
24 x 0.20
0.6
2.7
0.012
12
1
32 x 0.20
0.6
2.8
0.010
15
1.5
30 x 0.25
0.7
3.4
0.009
21
2.5
50 x 0.25
0.8
4.1
0.009
33