Non-sheathed
cables >> 60227 IEC 07
Single-core
non-sheathed cables with solid conductor for internal wiring for
a conductor temperature of 90°C.
Application:
- In dry rooms, apparatus, switch and distribution boards, for fixed
installation in conduits, over and under plaster and on insulated
supports over plaster. Direct laying in plaster is not permitted.
- Minimum bending radius: 4 times of maximum overall diameter.
Standard:
- ISIRI (607)07
- IEC (60227)07
- H05V2-U
Construction:
-
Annealed copper conductor, class 1.
-
PVC insulation, type E
- H05V2-U |
|
General
specification:
- Rated voltage: 300/500 V.
- Working temperature: Max. 90°C.
|
Cross-
sectional
area
Nom.
|
No.
of
wires x
diameter
Nom.
|
Insulation
thickness
Nom.
|
Overall
diameter
Max.
|
Insulation
resistance
at 70°C
Min.
|
Weight
Nom.
|
|
mm2
|
mm
|
mm
|
mm
|
|
kg/km
|
|
0.5
|
1
x 0.8
|
0.6
|
2.3
|
0.015
|
9
|
|
0.75
|
1
x 0.98
|
0.6
|
2.5
|
0.013
|
11
|
|
1
|
1
x 1.13
|
0.6
|
2.7
|
0.012
|
15
|
|
1.5
|
1
x 1.38
|
0.7
|
3.2
|
0.011
|
21
|
|
2.5
|
1
x 1.78
|
0.8
|
3.9
|
0.009
|
31
|
|