Non-sheathed cables >> 60227 IEC 06

Single-core non-sheathed cables with solid conductor for internal wiring for a conductor temperature of 70°C.

Application:
- In dry rooms, apparatus, switch and distribution boards, for fixed installation in conduits, over and under plaster and on insulated supports over plaster. Direct laying in plaster is not permitted.
- Minimum bending radius: 5 times of maximum overall diameter.
Standard:
- ISIRI (607)06
- IEC (60227)06
- H05V-K
Construction:
- Annealed copper conductor, class 5.
- PVC insulation, type C.

General specification:
- Rated voltage: 300/500 V.
- Working temperature: Max. 70°C.

Cross-
sectional
area
Nom.
No. of
wires x
diameter
Nom.
Insulation
thickness
Nom.
Overall
diameter
Max.
Insulation
resistance
at 70°C
Min.
Weight
Nom.
mm2
mm
mm
mm
kg/km
0.5
16 x 0.20
0.6
2.5
0.013
9
0.75
24 x 0.20
0.6
2.7
0.011
12
1
32 x 0.20
0.6
2.8
0.010
15