Non-sheathed cables >> 60227 IEC 02

Single-core non-sheathed cables with flexible conductor for general purposes.

Application:
- In dry rooms, apparatus switch and distribution boards, for fixed installation in conduits, over and under plaster and on insulated supports over plaster. Direct laying in plaster is not permitted.
- Minimum bending radius: 5 times of maximum overall diameter.

Standard:
- ISIRI (607)02
- IEC (60227)02
- H07V-k


Construction:
- Annealed copper conductor, class 5.
- PVC insulation, type C.

General specification:
- Rated voltage: 450/750 V.
- Working temperature: Max. 70°C.

Cross-
sectional
area
Nom.
No. of
wires x
diameter
Nom.
Insulation
thickness
Nom.
Overall
diameter
Max.
Insulation
resistance
at 70°C
Min.
Weight
Nom.
mm2
mm
mm
mm
kg/km
1.5
30 x 0.25
0.7
3.4
0.010
21
2.5
50 x 0.25
0.8
4.1
0.009
33
4
56 x 0.30
0.8
4.8
0.007
49
6
84 x 0.30
0.8
5.3
0.006
70
10
80 x 0.40
1.0
6.8
0.0056
125
16
126 x 0.40
1.0
8.1
0.0046
194
25
196 x 0.40
1.2
10.2

0.0044

297
35
297 x 0.40
1.2
11.7
0.0038
397
50
398 x 0.40
1.4
13.9
0.0037
551